SMCB Ring Main Circuit Breaker is pad mounted fully deadfront switchgear for up to 25.8kV, 630A underground system, combining puffer load break switches and vacuum fault interrupters. SMCB series switchgear incorporates grounding switches in every ways to provide safety and faster operation.
Every bushing in this switchgear is installed with one set of CT and voltage sensor each, so all the electrical values of connected distribution system can be measured. And, combined with SCADA-mate control based on SEL-551 relay or SEL-501-2 relay and RTU, this switchgear can be remotely operated from system control center.
- Field proven vacuum Interrupter ensures the safety and life- long interruption
- SF6 Gas Insulation Media which is enclosed in stainless steel tank sealed for life and maintenance free with less than 0.2% leakage rate per year
- Normal insulation and interruption performance even at an atmospheric gas pressure
- Unique and field proven puffer and heavy duty tulip-shaped contacts
- Internal power source through integrated capacitor-potential transformer combination for the control circuit's power
- Three phase group-operated mechanism offers regular close-open speed regardless of operating speed or method (manual or electrical)
- Front ground circuit bushings in every way offer easy cable testing
- Deadfront design and mechanical interlock between main and earth switch provides a high level of safety and efficient maintenance.
- Spring charge mechanism for fault interrupters ensures rapid O-CO performance
Specifications
|
Description |
SMCB-16 |
SMCB-26 |
|
Maximum System Voltage |
15 Kv |
25.8kV |
|
Rated Continuous Current |
630 A |
630 A |
|
Electrical Operating Time of CB (Close/Open) |
60/25ms |
60/25ms |
|
Electrical Operating Time of LBS (Close/Open) |
700 ms each |
700 ms each |
|
Minimum Clearing Time of CB |
2.7 cycle |
2.7cycle |
|
Number of Mechanical Operations of CB
Number of Mechanical Operations of LBS
Number of Mechanical Operations of Ground |
2,000 times 5,000 times 1,000 times |
2,000 times 5,000 times 1,000 times |
|
Short Time Withstand Current ( rms) |
20 kA (4 sec) |
12.5 kA (3sec) |
|
Breaking Capacity of CB |
20 kA |
12.5kA |
|
Insulation Level |
Lightning Impulse Withstand Voltage |
95 kV BIL |
125 kV BIL |
|
Power Frequency Withstand Voltage |
50 kV |
60 kV |
|
DC Voltage Withstand Voltage |
53 kV |
78 kV |
|
Partial Discharge Extinction Level |
19 kV |
19 kV |
|
Weight without Outer Enclosure |
670 Kg (2CB 2SW) |
|
|
Material |
stainless steel |
Packaging |
Wood packing |